Indoor Decorative Luminaire (Mirror Optic Type Philips TCS 36/236) with 2 no. 1200 mm 36 / 40 W Fluorescent Lamp
Utilization Factor: MO Fitting Reflection factor DRR Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.6 0.32 0.27 0.23 0.31 0.27 0.23 0.26 0.23 0.310 B 0.8 0.40 0.34 0.31 0.39 0.34 0.30 0.34 0.30 0.412 C 1.0 0.45 0.40 0.37 0.44 0.40 0.36 0.39 0.36 0.495 D 1.25 0.51 0.46 0.43 0.49 0.45 0.42 0.45 0.42 0.576 E 1.5 0.54 0.50 0.47 0.53 0.49 0.46 0.49 0.46 0.635 F 2.0 0.60 0.56 0.53 0.58 0.55 0.53 0.54 0.52 0.723 G 2.5 0.63 0.60 0.57 0.61 0.59 0.57 0.58 0.56 0.777 H 3.0 0.65 0.63 0.60 0.64 0.61 0.60 0.60 0.59 0.814 I 4.0 0.68 0.66 0.64 0.66 0.64 0.63 0.63 0.62 0.857 J 5.0 0.69 0.67 0.66 0.67 0.66 0.65 0.65 0.64 0.883 Note: The above figure is based on the efficiency of luminaire as 75 %.
-
Box Type Fitting with 1 no. 1200 mm Fluorescent Lamp and Stove Enameled Channel
Utilization Factor: Box Fitting Reflection factor Direct Ratio Floor 30 % 30 % 30 % Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 50 % 30 % 10 % Room Index Coefficient of Utilization A 0.6 0.29 0.23 0.18 0.27 0.21 0.17 0.24 0.20 0.16 0.27 B 0.8 0.42 0.34 0.28 0.38 0.30 0.25 0.33 0.27 0.23 0.31 C 1.0 0.48 0.40 0.33 0.42 0.36 0.31 0.38 0.32 0.27 0.37 D 1.25 0.55 0.47 0.40 0.48 0.42 0.36 0.42 0.37 0.32 0.43 E 1.5 0.59 0.52 0.45 0.52 0.45 0.40 0.46 0.39 0.36 0.48 F 2.0 0.67 0.59 0.53 0.58 0.53 0.47 0.51 0.46 0.41 0.55 G 2.5 0.72 0.64 0.58 0.63 0.57 0.52 0.55 0.50 0.46 0.60 H 3.0 0.76 0.69 0.63 0.66 0.61 0.56 0.57 0.54 0.50 0.65 I 4.0 0.81 0.75 0.71 0.71 0.66 0.62 0.61 0.57 0.55 0.70 J 5.0 0.86 0.80 0.75 0.74 0.69 0.66 0.64 0.61 0.57 0.74
Mainly Direct Fittings
-
Direct (A) Standard Dispersive Reflector for Gas filled Lamps and for 85 W & 125 W Mercury Lamps (type MB/U) and Sodium Vapour Lamps (Type SO). Also for Open top and Closed top Enamelled and Translucents Troughs for Fluorescent Lamps (type MCF/U). Typical Efficiency is 70 % (Down) and typical outline is given below:
Utilization Factor: Direct (Standard Dispersive Reflector) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.33 0.28 0.24 0.32 0.28 0.24 0.27 0.24 B 0.41 0.36 0.33 0.40 0.36 0.33 0.36 0.33 C 0.44 0.40 0.38 0.43 0.40 0.37 0.40 0.37 D 0.47 0.44 0.42 0.46 0.43 0.41 0.43 0.41 E 0.50 0.47 0.45 0.49 0.46 0.44 0.46 0.44 F 0.53 0.50 0.48 0.52 0.49 0.47 0.49 0.47 G 0.56 0.52 0.51 0.55 0.53 0.50 0.53 0.50 H 0.59 0.56 0.54 0.58 0.56 0.53 0.56 0.53 I 0.62 0.59 0.57 0.61 0.59 0.56 0.59 0.56 J 0.64 0.62 0.60 0.63 0.61 0.59 0.61 0.59 -
Direct (A) Dispersive Reflector for 250/400W Mercury Lamps (Type MA/V) and 80 / 400 W (MBF/U) Concentrating Enamelled Reflector for 80 / 125 W (MB/U) Mercury, Sodium (SO/H) and Gas filled Lamps. Typical efficiency is 60 % (Down) and typical outline is given below:
Utilization Factor: Direct (Dispersive Reflector) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.30 0.25 0.22 0.29 0.25 0.22 0.25 0.22 B 0.36 0.33 0.31 0.36 0.32 0.30 0.32 0.30 C 0.39 0.36 0.34 0.39 0.35 0.33 0.35 0.33 D 0.42 0.39 0.37 0.42 0.38 0.36 0.38 0.36 E 0.45 0.42 0.40 0.45 0.41 0.39 0.41 0.39 F 0.48 0.45 0.43 0.48 0.44 0.42 0.44 0.42 G 0.51 0.48 0.46 0.51 0.47 0.45 0.47 0.45 H 0.54 0.51 0.49 0.54 0.50 0.48 0.50 0.48 I 0.56 0.54 0.52 0.56 0.53 0.51 0.53 0.51 J 0.58 0.56 0.54 0.57 0.55 0.53 0.54 0.53 -
Direct (B) Reflectors with Enclosed Globe such as Industrial Diffusing Lighting for Gas filled Lampsor for Blended Light (MBT) Lamps. Also Open Reflector for Mercury Tungsten Lamps (MAT). Typical Efficiency is 50 to 60 % (Down) and typical outline is given below:
Utilization Factor: Direct (Reflector with Enclosed Globe) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.28 0.25 0.22 0.26 0.23 0.20 0.22 0.20 B 0.34 0.30 0.27 0.31 0.29 0.27 0.28 0.26 C 0.39 0.34 0.32 0.36 0.34 0.32 0.32 0.31 D 0.43 0.38 0.36 0.40 0.38 0.36 0.36 0.35 E 0.47 0.42 0.40 0.44 0.42 0.40 0.40 0.39 F 0.50 0.45 0.43 0.47 0.45 0.43 0.43 0.42 G 0.53 0.48 0.46 0.50 0.48 0.46 0.46 0.45 H 0.55 0.51 0.49 0.53 0.51 0.49 0.49 0.48 I 0.57 0.53 0.51 0.54 0.52 0.50 0.50 0.49 J 0.58 0.54 0.52 0.55 0.55 0.51 0.51 0.50 -
Semi-Direct Wide mouth Opal Fitting for Gas filled Lamps. Diffusing Fluorescent Fitting. Typical efficiency is 55 % (Down) & 16 % (Up) and typical outline is given below:
Utilization Factor: Semi-direct (Wide Mouth Opal) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.27 0.24 0.22 0.26 0.23 0.21 0.22 0.20 B 0.31 0.28 0.26 0.30 0.27 0.25 0.26 0.24 C 0.35 0.32 0.30 0.34 0.31 0.28 0.30 0.28 D 0.39 0.36 0.34 0.38 0.34 0.31 0.33 0.31 E 0.42 0.39 0.37 0.41 0.37 0.34 0.36 0.34 F 0.45 0.42 0.40 0.44 0.40 0.37 0.39 0.37 G 0.48 0.45 0.43 0.47 0.43 0.40 0.41 0.39 H 0.51 0.48 0.46 0.49 0.45 0.42 0.43 0.41 I 0.54 0.51 0.48 0.51 0.47 0.44 0.45 0.43 J 0.56 0.53 0.50 0.53 0.49 0.46 0.47 0.45 Note: In case of multi lamp fittings housing two to three lamps, the coefficient of utilization will be 0.85 to 0.9 times the figure given in above table.
Cover Glasses: When for mainly direct fitting, a fron cover of glass is fitted to reduce the brightness or to exclude dirt, an additional allowance must be made for the light absorption, depending on the shape, type and quality of the glass. As a general rule, the above figures should be multiplied by 0.7 for flashed opal, 0.75 for frosted and 0.9 for clear glass, but a definite figure can be obtained from the manufacturer.
-
Semi Direct Batten type and V-channel type Fittings for Fluorescent Lamps (Type MCF/U). Typical efficiency is 60 % (Down), 25 % (Up) and typical outline is given below:
Utilization Factor: Semi-direct (Batten Type) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.30 0.25 0.21 0.27 0.22 Not generally to be recommended with dark surroundings on account of the likelyhood of discomfirt glare. B 0.38 0.32 0.28 0.34 0.29 C 0.42 0.36 0.33 0.39 0.34 D 0.46 0.41 0.37 0.43 0.38 E 0.50 0.45 0.40 0.47 0.42 F 0.55 0.50 0.45 0.51 0.45 G 0.60 0.54 0.49 0.54 0.49 H 0.63 0.58 0.52 0.57 0.52 I 0.67 0.62 0.57 0.59 0.54 J 0.70 0.65 0.60 0.61 0.56
General Diffusing Fittings
-
General Diffusing. Enclosed Diffusing Fitting of Flashed Opal Glass. Typical efficiency is 45 % (Down), 35 % (Up) and typical outline is given below:
Utilization Factor: Diffusing (Enclosed) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.26 0.21 0.18 0.22 0.18 0.16 0.17 0.15 B 0.31 0.26 0.22 0.27 0.23 0.20 0.20 0.18 C 0.35 0.30 0.26 0.31 0.27 0.24 0.23 0.21 D 0.38 0.33 0.30 0.34 0.30 0.27 0.26 0.24 E 0.41 0.37 0.33 0.37 0.33 0.30 0.29 0.27 F 0.44 0.40 0.36 0.40 0.36 0.33 0.32 0.30 G 0.47 0.43 0.39 0.43 0.39 0.36 0.35 0.33 H 0.50 0.47 0.42 0.45 0.41 0.38 0.37 0.36 I 0.53 0.50 0.45 0.47 0.43 0.40 0.39 0.38 J 0.56 0.53 0.48 0.49 0.45 0.42 0.41 0.40 -
Frame type with Diffusing sides, open above, ribbed glass or louvered beneath, Suspended. Typical efficiency is 35 % (Down), 45 % (Up) and typical outline is given below:
Utilization Factor: Diffusing (Frame Type) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.26 0.23 0.21 0.23 0.21 B 0.32 0.29 0.27 0.28 0.26 C 0.35 0.32 0.31 0.31 0.29 D 0.38 0.35 0.34 0.34 0.32 E 0.41 0.38 0.37 0.37 0.35 F 0.44 0.41 0.40 0.40 0.38 G 0.47 0.44 0.43 0.42 0.41 H 0.50 0.47 0.46 0.44 0.43 I 0.53 0.50 0.49 0.46 0.45 J 0.55 0.52 0.51 0.48 0.46
Mainly Indirect Fittings
-
Semi Indirect. Open above, Louvered beneath. Typical efficiency is 20 % (Down), 55 % (Up) and typical outline is given below:
Utilization Factor: Semi-indirect Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.20 0.16 0.14 0.19 0.14 The coefficients are based on a 75% luminous efficiency of fitting, and will need additional judgament in proportion when using fittings of higher or liwer efficiency. These fittings are suitable for use in rooms with light coloured decorations. B 0.26 0.21 0.18 0.24 0.18 C 0.31 0.25 0.22 0.27 0.22 D 0.35 0.29 0.26 0.30 0.26 E 0.39 0.34 0.30 0.33 0.30 F 0.43 0.38 0.34 0.36 0.34 G 0.46 0.42 0.38 0.39 0.37 H 0.50 0.46 0.42 0.42 0.40 I 0.53 0.49 0.46 0.44 0.42 J 0.56 0.52 0.50 0.46 0.44 -
Indirect (A). Pendant Fittings and Throughs giving all their light output in an upward direction, but without sharp directional control of light. Typical efficiency is 75 % (Up) and typical outline is given below:
Utilization Factor: Indirect (Pendant) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.15 0.12 0.10 0.10 0.08 The coefficients are based on a 75% luminous efficiency of fitting, and will need additional judgament in proportion when using fittings of higher or liwer efficiency. These fittings are suitable for use in rooms with light coloured decorations. B 0.18 0.16 0.13 0.12 0.10 C 0.21 0.19 0.16 0.14 0.12 D 0.24 0.22 0.19 0.16 0.14 E 0.27 0.25 0.22 0.18 0.16 F 0.30 0.28 0.25 0.20 0.18 G 0.33 0.30 0.27 0.22 0.20 H 0.36 0.32 0.29 0.23 0.21 I 0.38 0.34 0.31 0.24 0.22 J 0.40 0.36 0.33 0.25 0.23 -
Indirect (B). Cornices, Recessed Covers and Collars giving all their light above Horizontal.
Utilization Factor: Indirect (Cornices) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.08 0.06 0.05 0.05 0.04 These coefficients are based on a 40% liminous efficiency of the fixture, but details of construction may vary this figure very considerably. B 0.10 0.08 0.07 0.07 0.06 C 0.12 0.10 0.09 0.08 0.07 D 0.13 0.11 0.10 0.09 0.08 E 0.15 0.13 0.11 0.10 0.09 F 0.17 0.15 0.13 0.11 0.10 G 0.18 0.16 0.15 0.12 0.11 H 0.19 0.18 0.16 0.13 0.12 I 0.21 0.20 0.18 0.14 0.13 J 0.22 0.21 0.20 0.15 0.14 -
Louvered Ceilings.
Utilization Factor: Indirect (Louvered Ceiling) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.21 0.18 0.17 Light angle 40o, Opaque louvers with reflection factor 75%, Ceiling cavity reflection factor 75%. No reflectors. B 0.25 0.21 0.20 C 0.28 0.24 0.23 D 0.30 0.27 0.26 E 0.32 0.29 0.28 F 0.34 0.31 0.30 G 0.36 0.33 0.32 H 0.37 0.35 0.34 I 0.38 0.36 0.36 J 0.39 0.37 0.37 -
Louvered Ceilings.
Utilization Factor: Indirect (Louvered Ceiling) Reflection factor Ceiling 70 % 50 % 30 % Wall 50 % 30 % 10 % 50 % 30 % 10 % 30 % 10 % Room Index Coefficient of Utilization A 0.23 0.17 0.14 Based on reflection factor of ceiling cavity 75%. Cavity reasonably free from obstructions and having depth not exceeding one third of its width. Absorption of translucent louvers 10%. B 0.28 0.24 0.20 C 0.34 0.29 0.25 D 0.38 0.33 0.30 E 0.42 0.38 0.35 F 0.46 0.43 0.40 G 0.49 0.46 0.43 H 0.52 0.49 0.47 I 0.55 0.52 0.50 J 0.57 0.55 0.53